Crossposting in r/BuildingAutomation and r/HVAC so I can hopefully get some code references. I have looked around but am clearly not Googling the right key words lol.
I am an electrician doing HVAC controls for a job and am trying to run 1/4" pressure tubing from RTUs to 2/3 of the way down the duct runs on the floor they serve per my engineer's requirements. What code covers how I'm supposed to safely run this pressure tubing through the HVAC duct shafts and shaft walls? The shafts are fire rated and there are fire dampers on each floor. I am only familiar with electrical code in the NEC/NFPA 70. What I found online was:
IMC 602.3.5 Pneumatic Tubing
Combustible pneumatic tubing exposed within a plenum shall be listed and labeled as having a peak optical density not greater than 0.50, an average optical density not greater than 0.15, and a flame spread distance not greater than 5 feet (1524 mm) when tested in accordance with UL 1820.
I understand that free air tubing is legal in the shaft if the tubing I use is listed and labeled. I know I need to have a sleeve penetrating the shaft walls to get the tubing inside the shaft. I do not understand if there are any vertical support/strapping requirements or "the tubing cannot touch the duct" type rules.
Do I just run the tubing where ever there's space in the shaft and hope the insulators and drywall guys don't kink it when they do their jobs? I can't wait until the shaft walls are up and then run the tubing, there is very limited open space around everything and it would be very difficult to fish after walls go up. Is it okay to ignore the shaft and instead drill holes through the top of the studs that surround the structural steel of the shaft and run the tubing inside the drywall sandwich of the shaft walls? That is what my foreman advised but he wasn't sure it was legal. Does anyone have relevant code references beyond the one I copy pasted above?